Please use this identifier to cite or link to this item: https://hdl.handle.net/20.500.13091/474
Title: Numerical comparison of thermal and hydraulic performances for heat exchangers having circular and elliptic cross-section
Authors: Doğan, Sercan
Darıcı, Selçuk
Özgören, Muammer
Keywords: Cfd
Cooling System
Elliptical Tubes
Heat Transfer
Thermal-Hydraulic Performance
Pressure-Drop Characteristics
Air-Side Performance
Membrane Tube Bank
Plate-Fin
Friction Characteristics
Fluid-Flow
Pcm Solidification
Nanoparticles
Vortex
Model
Publisher: PERGAMON-ELSEVIER SCIENCE LTD
Abstract: The plain fin and circular tubes are generally used in heat exchangers of cooling systems. Numerous studies aiming at enhancing the thermal and hydraulic performances of this type of heat exchangers by changing the fin geometries are present in literature. In the present study, thermal and hydraulic performances of the heat exchangers with circular and elliptical tube have been compared using computational fluid dynamic method. Initially, the validation and comparison were done for the obtained data of the finned and circular tube design with respect to the performance results of the finned and circular tube design in the literature. The ellipticity ratios for the staggered arrangements of heat exchangers were changed within the range of b/a = 0.307-1.0. Numerical studies were performed with ANSYS-Fluent software within the range of Re = 750-2850 based on the fin spacing. As a result of the numerical validation studies, all analyses were solved by utilizing the SST k-omega turbulence model yielding closer values to the available studies similar to literature. Colburn factor j, friction factor f, JF values being the efficiency index and normalized j*, f* and JF* values were calculated and presented graphically. Moreover, temperature contours and streamline patterns were visually presented to evaluate the flow structures around the six different arrangements and to explain the physical reasons of pressure drop and heat transfer phenomena. The largest values of the Colburn factor j and the friction factor f known respectively as an indicator of heat transfer and a measure of pressure drop were obtained for the circular-tube-design ratio of b/a = 1.0 when compared to the other arrangements. According to the JF values, which is the efficiency index and the integrated outcome of heat transfer and pressure drop, the best result was obtained for the model with the diameter ratio of b/a = 0.307. Variations of the JF values for the arrangements of b/a = 0.333 and b/a = 0.307 depending on Reynolds numbers were found to be significantly close to each other. Finally, it is demonstrated that elliptical cross-section tubes with a better design in terms of lower pressure drop and less separated flow structures can be preferred in heat exchanger applications in order to provide energy saving. (C) 2019 Elsevier Ltd. All rights reserved.
URI: https://doi.org/10.1016/j.ijheatmasstransfer.2019.118731
https://hdl.handle.net/20.500.13091/474
ISSN: 0017-9310
1879-2189
Appears in Collections:Mühendislik ve Doğa Bilimleri Fakültesi Koleksiyonu
Scopus İndeksli Yayınlar Koleksiyonu / Scopus Indexed Publications Collections
WoS İndeksli Yayınlar Koleksiyonu / WoS Indexed Publications Collections

Files in This Item:
File SizeFormat 
1-s2.0-S0017931019314620-main.pdf
  Until 2030-01-01
5.23 MBAdobe PDFView/Open    Request a copy
Show full item record



CORE Recommender

SCOPUSTM   
Citations

15
checked on Apr 20, 2024

WEB OF SCIENCETM
Citations

32
checked on Apr 20, 2024

Page view(s)

88
checked on Apr 22, 2024

Google ScholarTM

Check




Altmetric


Items in GCRIS Repository are protected by copyright, with all rights reserved, unless otherwise indicated.