Title: | Voltage sensitivity-based demand-side management to reduce voltage unbalance in islanded microgrids | Authors: | Çimen, Halil Çetinkaya, Nurettin |
Keywords: | Power Grids Power Distribution Control Distributed Power Generation Voltage Control Power Supply Quality Photovoltaic Power Systems Electric Vehicles Power Distribution Faults Voltage Sensitivity-Based Demand-Side Management Islanded Microgrids Distribution Grid Demand Management Dynamic Grid Advanced Control System Islanded Mg Single-Phase Roof-Mounted Pv Plants Dsm Voltage Unbalance Problem Thermostatically Controlled Loads Controllable Loads Control Algorithm Voltage Sensitivity Matrix Controlled Tcls Compensation Loads |
Issue Date: | 2019 | Publisher: | INST ENGINEERING TECHNOLOGY-IET | Abstract: | Microgrids (MG) provide advantages such as providing energy supply to areas far from the distribution grid, efficient use of resources by supporting demand management and having a more dynamic grid. However, if an advanced control system is not implemented in the islanded MG, problems of power quality may arise. One of these problems is the voltage unbalance. Increasing the number of single-phase roof-mounted PV plants and the number of electric vehicle charging stations in recent times may negatively affect voltage unbalance. One of the methods used to mitigate this problem is the demand-side management (DSM). Here, a solution method based on DSM is presented for the voltage unbalance problem that may occur in an islanded MG. Thermostatically controlled loads, which are often used for DSM, are preferred as controllable loads. A new and novel control algorithm based on voltage sensitivity have been developed. Effects of TCLs on different buses and phases are determined with voltage sensitivity matrix including neutral components. The proposed control algorithm reduces successfully both the voltage unbalance factor and the number of controlled TCLs. The algorithm was tested with the PSCAD/EMTDC analysis software. | URI: | https://doi.org/10.1049/iet-rpg.2018.5603 https://hdl.handle.net/20.500.13091/376 |
ISSN: | 1752-1416 1752-1424 |
Appears in Collections: | Mühendislik ve Doğa Bilimleri Fakültesi Koleksiyonu Scopus İndeksli Yayınlar Koleksiyonu / Scopus Indexed Publications Collections WoS İndeksli Yayınlar Koleksiyonu / WoS Indexed Publications Collections |
Files in This Item:
File | Size | Format | |
---|---|---|---|
IET Renewable Power Gen - 2019 - imen - Voltage sensitivity‐based demand‐side management to reduce voltage unbalance in.pdf Until 2030-01-01 | 1.7 MB | Adobe PDF | View/Open Request a copy |
CORE Recommender
SCOPUSTM
Citations
10
checked on May 27, 2023
WEB OF SCIENCETM
Citations
9
checked on Jan 30, 2023
Page view(s)
64
checked on May 22, 2023
Google ScholarTM
Check
Altmetric
Items in GCRIS Repository are protected by copyright, with all rights reserved, unless otherwise indicated.